Study on the Transient Characteristics of 1100kV VFTO
全文录用
wu xiu / Wuhan University of Science and Technology
The very fast transient overvoltage (VFTO) generated by switching disconnector (DS) in gas insulated substation (GIS) with the features of high amplitude, short rise-time and complex frequency components, may cause damage to the insulation of electrical equipment. Therefore, in order to improve the safety performance of GIS equipment, it is very important to study the transient characteristics of VFTO. Four typical transient parameters: rise-time tr, breakdown steepness k, decay time td, and voltage overshoot coefficient H are defined for the purpose of describing the VFTO waveform characteristics accurately. The typical transient statistical law of VFTO waveform is studied. The results reveal that① For UHV voltage level VFTO, the rise time tr is greater than 10ns but no more than 30ns. ②The average decay time td of 1100kV VFTO is about 30μs and the average voltage overshoot coefficient H is less than 1. ③The breakdown voltage acts out polarity effect apparently. The positive breakdown voltage is about 1042kV, which is much greater than the negative breakdown voltage with -607kV value. ④With the increasing of breakdown voltage, the maximum value of VFTO peak waveform and the value of H become higher. At the same time, VFTO is oscillating severely, which results in the decay time td and breakdown steepness k change in the same tendency of H.
重要日期
  • 会议日期

    10月22日

    2017

    10月25日

    2017

  • 01月04日 2017

    摘要录用通知日期

  • 03月10日 2017

    初稿录用通知日期

  • 06月30日 2017

    终稿截稿日期

  • 10月25日 2017

    注册截止日期

联系方式
  • ice********
  • +86*********
移动端
在手机上打开
小程序
打开微信小程序
客服
扫码或点此咨询